Difference between revisions of "Pipes"
		
		
		
		
		
		Jump to navigation
		Jump to search
		
				
		
		
	
Jenny Hill (talk | contribs)  | 
				Jenny Hill (talk | contribs)   | 
				||
| Line 1: | Line 1: | ||
| + | <div class="col-md-8">  | ||
*Perforated pipes should be continuously perforated, smooth interior HDPE (or equivalent material) with a minimum inside diameter of 100 mm.    | *Perforated pipes should be continuously perforated, smooth interior HDPE (or equivalent material) with a minimum inside diameter of 100 mm.    | ||
**Where freezing is a concern, horizontal underdrain pipes should be over-sized to a minimum 200 mm diameter.    | **Where freezing is a concern, horizontal underdrain pipes should be over-sized to a minimum 200 mm diameter.    | ||
| Line 9: | Line 10: | ||
*Non-perforated pipes should be used for conveyance to and away from the facility, including overflow.  | *Non-perforated pipes should be used for conveyance to and away from the facility, including overflow.  | ||
**To function correctly, the capacity of the overflow pipes must be greater than the inlet(s).  | **To function correctly, the capacity of the overflow pipes must be greater than the inlet(s).  | ||
| − | + | </div>  | |
| + | <div class="col-md-4">  | ||
| + | <gallery mode="packed" widths=300px heights=300px>  | ||
| + | Perforated Pipe 550x550.jpg| Pipe  | ||
| + | </gallery>  | ||
| + | </div>  | ||
| + | <div class="col-md-12">  | ||
[[Category:Materials]]  | [[Category:Materials]]  | ||
Revision as of 15:03, 11 July 2017
- Perforated pipes should be continuously perforated, smooth interior HDPE (or equivalent material) with a minimum inside diameter of 100 mm.
- Where freezing is a concern, horizontal underdrain pipes should be over-sized to a minimum 200 mm diameter.
 - Perforations should be 10 mm in diameter and distributed at least every 90 deg around the pipe.
 
 - All underdrains should be capped on the upstream end.
 - At least one vertical well per BMP is recommended, for inspection and monitoring water level.
- Well(s), of 100 - 150 mm diameter perforated pipe, should extend to the bottom of the facility.
 - Where a horizontal underdrain is being installed, an upstream and a downstream well should be coupled to the underdrain pipe. The pair of wells can then be used to flush out the length of underdrain if required.
 - The exposed tops of all wells should be fitted with lockable caps.
 
 - Non-perforated pipes should be used for conveyance to and away from the facility, including overflow.
- To function correctly, the capacity of the overflow pipes must be greater than the inlet(s).