|  | *''f''' = design infiltration rate (mm/hr) |  | *''f''' = design infiltration rate (mm/hr) | 
|  | *''t'' = [[drainage time|time permitted for ponding to infiltrate]] (hrs) (typically 48 hours)}} |  | *''t'' = [[drainage time|time permitted for ponding to infiltrate]] (hrs) (typically 48 hours)}} | 
|  | + |  | 
|  | + | ===Outlet=== | 
|  | + | Detention time | 
|  | + | A detention time of 24 hours should be targeted in all instances. Where this necessaitates a very low outflow, a [[Flow control#Vo|vortex valve or similar is recommended over an orifice or pipe restiction. The detention time is approximated by the drawdown time. | 
|  | + |  | 
|  | + | The drawdown time in the pond can be estimated using Equation 4.10. Equation 4.10 is the classic falling head orifice equation which assumes a constant pond surface area. This assumption is generally not valid, and a more accurate estimation can be made if Equation 4.10 is solved as a differential equation. This is easily done if the relationship between pond surface area and pond depth is approximated using a linear regression. | 
|  | + |  | 
|  | + | Equation 4.10: Drawdown Time | 
|  | + |  | 
|  | + | t = start fraction 2 A subscript p over C A subscript o left-parenthesis 2 g right-parenthesis superscript 0 point 5 end fraction left-parenthesis h subscript 1 superscript 0 point 5 minus h subscript 2 superscript 0 point 5 right-parenthesis | 
|  | + |  | 
|  | + | or if a relationship between Ap and h is known (i.e., A = C2h + C3) | 
|  | + |  | 
|  | + | t = start fraction 0 point 66 C subscript 2 h superscript 1 point 5 + 2 C subscript 3 h superscript 0 point 5 over 2 point 75 A subscript o end fraction | 
|  | + |  | 
|  | + | where: | 
|  | + |  | 
|  | + | t | 
|  | + | drawdown time in seconds | 
|  | + | Ap | 
|  | + | surface area of the pond(m²) | 
|  | + | C | 
|  | + | discharge coefficient (typically 0.63) | 
|  | + | A0 | 
|  | + | cross-sectional area of the orifice(m²) | 
|  | + | g | 
|  | + | gravitational acceleration constant (9.81,/s2) | 
|  | + | h1 | 
|  | + | starting water elevation above the orifice (m) | 
|  | + | h2 | 
|  | + | ending water elevation above the orifice (m) | 
|  | + | C2 | 
|  | + | slope coefficient from the area-depth linear regression | 
|  | + | C3 | 
|  | + | intercept from the area-depth linear regression | 
|  | + |  | 
|  | + | <ref>Ontario Ministry of Environment. (2003). Stormwater Management Planning and Design Manual. Retrieved January 15, 2017, from https://www.ontario.ca/document/stormwater-management-planning-and-design-manual/stormwater-management-plan-and-swmp-design</ref> | 
|  | + |  | 
|  |  |  |  | 